Off-Load Distribution Transformer

Off-Load Distribution Transformer
Business Type Manufacturer, Exporter, Supplier
Winding Material Copper With Multiple Paper Covering
Frequency 50/60 Hz
Type Indoor/ Outdoor
Click to view more

Preferred Buyer From

Location India ( Madhya Pradesh only) & All other countries

Product Details

Voltage Class
3.3, 6.6, 11, 22, 33 KV
Vector Group
Dyn11 or other specified by customer
No. of Phase
3 Phases
Tap Range
±10 %, +5% in 2.5% Steps or as per Requirement of Customer.
Applicable Standards
IS-1180:2014 (Part-1), IS-2026, IEC 60076
Painting
Epoxy or specified by customer
Brand
Electrotech

Details :

  • 200 kva Off Load Transformer
  • 315 kva Off Load Transformer
  • 400 kva Off Load Transformer
  • 500 kva Transformer in Gwalior
  • 630 kva Off Load Transformer
  • 750 kva Off Load Transformer
  • 800 kva Off Load Transformer
  • 1000 kva Off Load Transformer
  • 1250 kva Off Load Transformer
  • 1600 kva Off Load Transformer
  • 2000 kva Off Load Transformer
  • 2500 kva Off Load Transformer
  • 3000 kva Off Load Transformer
  • 3500 kva Off Load Transformer
  • 4000 kva Off Load Transformer
  • 4500 kva Off Load Transformer
  • 5000 kva Off Load Transformer

Yes! I am interested


Maximum Total Losses Upto 11 KV Class Transformers As Per BIS-1180:2014(Part-1)

Sr. No. KVA Impedance % Maximum Total Loss (W) @ 75˚ Celsius
LEVEL 1 LEVEL 2 LEVEL 3
0.5 1 0.5 1 0.5 1
1 250 4.5 1050 3150 980 2930 920 2700
2 315 4.5 1100 3275 1025 3100 955 2750
3 400 4.5 1300 3875 1225 3450 1150 3330
4 500 4.5 1600 4750 1510 4300 1430 4100
5 630 4.5 2000 5855 1860 5300 1745 4850
6 800 5 2459 7300 2287 6402 2147 5837
7 1000 5 3000 9000 2790 7700 2620 7000
8 1250 5 3600 10750 3300 9200 3220 8400
9 1600 6.25 4500 13500 4200 11800 3970 11300
10 2000 6.25 5400 17000 5050 15000 4790 14100
11 2500 6.25 6500 20000 6150 18500 5900 17500

Note: For Transformer having voltage class 22 Kv then permissible total loss shall not exceed by 5% of total loss as per above table and for 33 Kv Class permissible total loss shall not exceed by 7.5% of total loss as per above table. 